Building code profiles

Updated 5 min readWorks without an account

A building code profile sets the numbers the Review panel checks your stairs, railings, rooms and escape windows against. Pick the code for where you will build, from the IRC in the US to the Approved Documents in England.

Choose a building code

The plan summary open from the chip at the top left
  1. Step 1: Open the plan summary

    Click the chip at the top left that shows the area and rooms, or press ⌥3.

  2. Step 2: Find Building code

    Scroll to Building. Below the areas, pick a code in Building code. The line under it sums up its main rules.

  3. Step 3: Check the plan again

    Open Review with ⇧I. Every check now uses the new code, and the messages cite its sections.

The codes on offer

Each table lists the rules one profile checks, with the value as the source prints it, the clause it comes from and how sure we are. Messages show values in the project’s units. A rule a code does not set is not in its table and is not checked against that code. The fixed checks below apply under every code, and Generic lists rules of thumb because it cites no code. Room sizes apply only to rooms with that Room type.

Sources and how sure we are. Every number comes from a published document, cited with its edition and clause. Evidence “primary” means we read the value in the document itself. Evidence “secondary” means we read it in a copy, such as an adopting jurisdiction’s text or a reliable summary. Evidence “unverified” means we have not yet confirmed it in the current edition, and the note says why. Rules marked not checked yet are listed because the code sets them, but FloorGen does not measure your plan against them, so they never raise a warning.

IRC (US)

IRC (US): United States (where the 2021 IRC is adopted)
RuleValueClauseEvidence
Riser, maximum7¾ in (197 mm)IRC 2021 R311.7.5.1 (opens in a new tab)primary
Going (tread), minimum10 in (254 mm)IRC 2021 R311.7.5.2 (opens in a new tab)primary
Stair width, minimum36 in (914 mm)IRC 2021 R311.7.1 (opens in a new tab)primary
Spiral stair riser, maximum9½ in (241 mm)IRC 2021 R311.7.10.1 (opens in a new tab)secondarytreads are measured on the walkline, 12 in out from the column (its radius held to 24½ in); headroom 6 ft 6 in is not checked
Spiral stair tread at the walking line, minimum6¾ in (171 mm)IRC 2021 R311.7.10.1 (opens in a new tab)secondarytreads are measured on the walkline, 12 in out from the column (its radius held to 24½ in); headroom 6 ft 6 in is not checked
Spiral stair clear width, minimum26 in (660 mm)IRC 2021 R311.7.10.1 (opens in a new tab)secondarytreads are measured on the walkline, 12 in out from the column (its radius held to 24½ in); headroom 6 ft 6 in is not checked
Stair headroom, minimum80 in (2.032 m)IRC 2021 R311.7.2 (opens in a new tab)primary
Landing length, minimum36 in (914 mm)IRC 2021 R311.7.6 (opens in a new tab)primary
Handrail height, minimum34 in (864 mm)IRC 2021 R311.7.8.1 (opens in a new tab)primary
Handrail height, maximum38 in (965 mm)IRC 2021 R311.7.8.1 (opens in a new tab)primary
Handrail needed from this many risers4IRC 2021 R311.7.8 (opens in a new tab)secondary
Guard height, minimum36 in (914 mm)IRC 2021 R312.1.2 (opens in a new tab)primary
Guard needed from a drop of30 in (762 mm)IRC 2021 R312.1.1 (opens in a new tab)primary
Rise of one flight, maximum151 in (3.835 m)IRC 2021 R311.7.3 (opens in a new tab)primary
Bedroom, minimum floor area70 ft² (6.5 m²)IRC 2021 R304.1 (opens in a new tab)primary
Living room, minimum floor area70 ft² (6.5 m²)IRC 2021 R304.1 (opens in a new tab)primary
Dining room, minimum floor area70 ft² (6.5 m²)IRC 2021 R304.1 (opens in a new tab)primary
Study, minimum floor area70 ft² (6.5 m²)IRC 2021 R304.1 (opens in a new tab)primary
Kids room, minimum floor area70 ft² (6.5 m²)IRC 2021 R304.1 (opens in a new tab)primary
Bedroom, minimum width7 ft (2.134 m)IRC 2021 R304.2 (opens in a new tab)primary
Living room, minimum width7 ft (2.134 m)IRC 2021 R304.2 (opens in a new tab)primary
Dining room, minimum width7 ft (2.134 m)IRC 2021 R304.2 (opens in a new tab)primary
Study, minimum width7 ft (2.134 m)IRC 2021 R304.2 (opens in a new tab)primary
Kids room, minimum width7 ft (2.134 m)IRC 2021 R304.2 (opens in a new tab)primary
Ceiling height, habitable rooms84 in (2.134 m)IRC 2021 R305.1 (opens in a new tab)primary
Ceiling height, bathrooms and laundry80 in (2.032 m)IRC 2021 R305.1 (opens in a new tab)primary
Ceiling height, other basement rooms80 in (2.032 m)IRC 2021 R305.1.1 (opens in a new tab)primary
Escape opening, area5.7 ft² (0.53 m²)IRC 2021 R310.2.1 (opens in a new tab)primary
Escape opening, area on the grade floor5 ft² (0.46 m²)IRC 2021 R310.2.1 (opens in a new tab)primary
Escape opening, width20 in (508 mm)IRC 2021 R310.2.2 (opens in a new tab)primary
Escape opening, height24 in (610 mm)IRC 2021 R310.2.2 (opens in a new tab)primary
Escape opening, highest sill44 in (1.118 m)IRC 2021 R310.2.3 (opens in a new tab)primary
Wall outlet, farthest from any point along the wall6 ft (1.829 m)IRC 2021 E3901.2 (opens in a new tab)secondary
Wall space that needs outlets, from a width of2 ft (610 mm)IRC 2021 E3901.2 (opens in a new tab)secondary
Floor outlet counts for a wall within18 in (457 mm)IRC 2021 E3901.2 (opens in a new tab)secondary
Escape opening counts as grade-floor within this height of the ground44 in (1.118 m)IRC 2021 R202 (opens in a new tab)secondaryDefinition read in an ICC 2018 summary; the 2021 exception names grade-floor openings only
Window fall protection, opening lower than this above the floor24 in (610 mm)IRC 2021 R312.2.1 (opens in a new tab)primary
Window fall protection, opening higher than this above the ground72 in (1.829 m)IRC 2021 R312.2.1 (opens in a new tab)primary
Hallway width, minimum3 ft (914 mm)IRC 2021 R311.6 (opens in a new tab)primary
Openings from a garage into a bedroom, allowed0IRC 2021 R302.5.1 (opens in a new tab)secondary
Window glass, share of floor area, minimum8%IRC 2021 R303.1 (opens in a new tab)secondary
Openable window area, share of floor area, minimum4%IRC 2021 R303.1 (opens in a new tab)secondary
Egress door to outside, clear width32 in (813 mm)IRC 2021 R311.2 (opens in a new tab)primary
Egress door to outside, clear height78 in (1.981 m)IRC 2021 R311.2 (opens in a new tab)primary
Bathroom window glass without an exhaust fan, minimum3 ft² (0.28 m²)IRC 2021 R303.3 (opens in a new tab)primaryhalf of it openable; not needed with artificial light and a local exhaust to outdoors
WC or basin centreline to a side wall or fixture, minimum15 in (381 mm)IRC 2021 P2705.1 (opens in a new tab)primary
Clear floor in front of a WC or basin, minimum21 in (533 mm)IRC 2021 P2705.1 (opens in a new tab)primary
Clear floor in front of a shower opening, minimum24 in (610 mm)IRC 2021 R307.1 (opens in a new tab)primaryFigure R307.1: clear in front of the shower opening
Shower floor area, minimum900 in² (0.58 m²)IRC 2021 P2708.1 (opens in a new tab)primaryfinished interior, kept with a fold-down seat folded up
Shower, smallest side30 in (762 mm)IRC 2021 P2708.1 (opens in a new tab)primary
Shower, smallest side with the larger floor25 in (635 mm)IRC 2021 P2708.1 (opens in a new tab)primaryexception 2
Shower floor area with a narrower side, minimum1300 in² (0.84 m²)IRC 2021 P2708.1 (opens in a new tab)primaryexception 2

NBC Canada 2020

NBC Canada 2020: Canada (Part 9 houses; not Ontario, which has the OBC)
RuleValueClauseEvidence
Riser, minimum125 mmNBC 2020 Table 9.8.4.1 (opens in a new tab)secondary
Riser, maximum200 mmNBC 2020 Table 9.8.4.1 (opens in a new tab)secondary
Going (tread), minimum255 mmNBC 2020 Table 9.8.4.2 (opens in a new tab)secondary
Going (tread), maximum355 mmNBC 2020 Table 9.8.4.2 (opens in a new tab)secondary
Stair width, minimum860 mmNBC 2020 9.8.2.1 (opens in a new tab)secondary
Stair headroom, minimum1950 mm (1.95 m)NBC 2020 9.8.2.2 (opens in a new tab)secondary
Handrail height, minimum865 mmNBC 2020 9.8.7.4 (opens in a new tab)secondary
Guard height, minimum900 mmNBC 2020 9.8.8.3 (opens in a new tab)primarywithin dwelling units, and outside where the walking surface is at most 1800 mm above the ground
Guard height, higher walking surface1070 mm (1.07 m)NBC 2020 9.8.8.3 (opens in a new tab)primary
Taller guard above ground level of1800 mm (1.8 m)NBC 2020 9.8.8.3 (opens in a new tab)primary
Escape opening, area0.35 m²NBC 2020 9.9.10.1 (opens in a new tab)primarynot required where the suite is sprinklered (Sentence (1)), which the plan does not record
Escape opening, width380 mmNBC 2020 9.9.10.1 (opens in a new tab)primary
Escape opening, height380 mmNBC 2020 9.9.10.1 (opens in a new tab)primary
Guard needed from a drop of600 mmNBC 2020 9.8.8.1 (opens in a new tab)primary
Window fall protection, opening lower than this above the floor900 mmNBC 2020 9.8.8.1 (opens in a new tab)primarySentence (5): openable windows in residential occupancies; a guard or a 100 mm opening limit
Window fall protection, opening higher than this above the ground1800 mm (1.8 m)NBC 2020 9.8.8.1 (opens in a new tab)primary
Ceiling height, habitable rooms2100 mm (2.1 m)NBC 2020 Table 9.5.3.1 (opens in a new tab)primaryliving, dining, kitchen, bedrooms, other habitable rooms, halls; 1.95 m in a secondary suite (9.5.3.1.(2)) is not modelled
Secondary suite separation, sound transmission class, minimum43NBC 2020 9.11.1.1.(2) (opens in a new tab)secondaryHouse with a secondary suite: construction with an STC of at least 43, or the listed resilient-channel assembly
Secondary suite separation, apparent sound transmission class, minimum40NBC 2020 9.11.1.1.(2) (opens in a new tab)secondaryOr a separating assembly and adjoining constructions with an ASTC of at least 40
Handrail height, maximum1070 mm (1.07 m)not checked yetNBC 2020 9.8.7.4 (opens in a new tab)unverified865–965 mm in general and 1070 mm on a guard per some readings, 1070 mm per the BCBC copy: sources disagree
Ceiling height, bathrooms and laundry2100 mm (2.1 m)not checked yetNBC 2020 Table 9.5.3.1 (opens in a new tab)unverifiedbathrooms, WCs and laundries above grade only; the check does not yet tell above-grade wet rooms from basement ones
Window well, clear space in front of an escape window760 mmnot checked yetNBC 2020 9.9.10.1 (opens in a new tab)unverifiedclear space in front of an escape window that opens into a well (Sentence (3)), read in the 2020 text; window wells are not checked yet

OBC (Ontario)

OBC (Ontario): Ontario
RuleValueClauseEvidence
Riser, minimum125 mmOBC 2024 Table 9.8.4.1 (opens in a new tab)unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text
Riser, maximum200 mmOBC 2024 Table 9.8.4.1 (opens in a new tab)unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text
Going (tread), minimum255 mmOBC 2024 Table 9.8.4.2 (opens in a new tab)unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text
Going (tread), maximum355 mmOBC 2024 Table 9.8.4.2 (opens in a new tab)unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text
Stair width, minimum860 mmOBC 2024 9.8.2.1 (opens in a new tab)unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text
Stair headroom, minimum1950 mm (1.95 m)OBC 2024 9.8.2.2 (opens in a new tab)unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text
Handrail height, minimum865 mmOBC 2024 9.8.7.4 (opens in a new tab)unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text
Guard height, minimum900 mmOBC 2024 9.8.8.3 (opens in a new tab)secondary
Guard height, higher walking surface1070 mm (1.07 m)OBC 2024 9.8.8.3 (opens in a new tab)secondary
Taller guard above ground level of1800 mm (1.8 m)OBC 2024 9.8.8.3 (opens in a new tab)secondary
Guard needed from a drop of600 mmOBC 2024 9.8.8.1 (opens in a new tab)secondary
Window fall protection, opening lower than this above the floor900 mmOBC 2024 9.8.8.1 (opens in a new tab)secondarySentence (5), as the NBC; 480 mm was the 2012 OBC
Window fall protection, opening higher than this above the ground1800 mm (1.8 m)OBC 2024 9.8.8.1 (opens in a new tab)secondary
Escape opening, area0.35 m²OBC 2024 9.9.10.1 (opens in a new tab)secondary
Escape opening, width380 mmOBC 2024 9.9.10.1 (opens in a new tab)secondary
Escape opening, height380 mmOBC 2024 9.9.10.1 (opens in a new tab)secondary
Escape opening, highest sill1000 mm (1 m)OBC 2024 9.9.10.1 (opens in a new tab)secondary
Living room, minimum floor area13.5 m²not checked yetOBC 2024 9.5.3A.1 (opens in a new tab)unverified11 m² where living, dining and kitchen are combined in a unit sleeping two or fewer; smaller allowed where shown adequate (9.5.1.3)
Bedroom, minimum floor area7 m²not checked yetOBC 2024 9.5.3D.1 (opens in a new tab)unverified6 m² with built-in cabinets; one bedroom 9.8 m² (8.8 m² with built-ins, 9.5.3D.2); 4.2 m² combined with another space (9.5.3D.3)
Kitchen, minimum floor area4.2 m²not checked yetOBC 2024 9.5.3C.1 (opens in a new tab)unverified3.7 m² in a unit sleeping two or fewer
Dining room, minimum floor area7 m²not checked yetOBC 2024 9.5.3B.1 (opens in a new tab)unverifiedas a separate room; 3.25 m² combined with another space
Ceiling height, habitable rooms2300 mm (2.3 m)not checked yetOBC 2024 Table 9.5.3.1 (opens in a new tab)unverifiedover 75% of the required area of living, dining and kitchen spaces, 2100 mm at any point; bedrooms 2300 mm over 50% or 2100 mm over all; part-room heights and the per-room split are not modelled
Window well, clear space in front of an escape window550 mmnot checked yetOBC 2024 9.9.10.1 (opens in a new tab)unverifiedSentence (3), clear space in front of an escape window that opens into a well (760 mm in the NBC); window wells are not checked yet

BCBC (British Columbia)

BCBC (British Columbia): British Columbia (Part 9 houses)
RuleValueClauseEvidence
Riser, minimum125 mmBCBC 2024 9.8.4.1 (opens in a new tab)secondaryPrivate stairs, as summarised for secondary suites
Riser, maximum200 mmBCBC 2024 9.8.4.1 (opens in a new tab)secondaryPrivate stairs, as summarised for secondary suites
Going (tread), minimum255 mmBCBC 2024 Table 9.8.4.2 (opens in a new tab)unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same)
Going (tread), maximum355 mmBCBC 2024 Table 9.8.4.2 (opens in a new tab)unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same)
Stair width, minimum860 mmBCBC 2024 9.8.2.1.(2) (opens in a new tab)secondaryExit stairs serving a house with a secondary suite
Stair headroom, minimum1950 mm (1.95 m)BCBC 2024 9.8.2.2.(3) (opens in a new tab)secondaryStairs serving a house with a secondary suite
Handrail height, minimum865 mmBCBC 2024 9.8.7.4 (opens in a new tab)unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same)
Guard height, minimum900 mmBCBC 2024 9.8.8.3 (opens in a new tab)unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same)
Guard height, higher walking surface1070 mm (1.07 m)BCBC 2024 9.8.8.3 (opens in a new tab)unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same)
Taller guard above ground level of1800 mm (1.8 m)BCBC 2024 9.8.8.3 (opens in a new tab)unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same)
Guard needed from a drop of600 mmBCBC 2024 9.8.8.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same)
Window fall protection, opening lower than this above the floor900 mmBCBC 2024 9.8.8.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same)
Window fall protection, opening higher than this above the ground1800 mm (1.8 m)BCBC 2024 9.8.8.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same)
Escape opening, area0.35 m²BCBC 2024 9.9.10.1 (opens in a new tab)secondaryBedroom window; summarised for secondary suites
Escape opening, width380 mmBCBC 2024 9.9.10.1 (opens in a new tab)secondaryNo dimension under 380 mm
Escape opening, height380 mmBCBC 2024 9.9.10.1 (opens in a new tab)secondaryNo dimension under 380 mm
Secondary suite separation, fire-resistance rating, lowest option (minutes)15BCBC 2024 9.10.9.16 (opens in a new tab)secondaryMinutes. 15 where every smoke alarm in the house is photo-electric and interconnected (9.10.19.5.(2)); 30 with an extra photo-electric alarm in each unit and common space; 45 otherwise; none if sprinklered
Secondary suite separation, fire-resistance rating with no alarm or sprinkler credit (minutes)45BCBC 2024 9.10.9.16 (opens in a new tab)secondaryMinutes, with no alarm or sprinkler credit (9.10.19.5.(3))
Secondary suite separation, sound transmission class, minimum43BCBC 2024 9.11.1.1.(2) (opens in a new tab)secondaryOr the listed resilient-channel assembly
Secondary suite separation, apparent sound transmission class, minimum40BCBC 2024 9.11.1.1.(2) (opens in a new tab)secondary
Handrail height, maximum1070 mm (1.07 m)not checked yetBCBC 2024 9.8.7.4.(2) (opens in a new tab)unverified865 to 1070 mm in the 2018 BCBC; the 2024 text was not opened

NBC Alberta Edition 2023

NBC Alberta Edition 2023: Alberta (Part 9 houses)
RuleValueClauseEvidence
Riser, minimum125 mmNBC(AE) 2023 Table 9.8.4.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Riser, maximum200 mmNBC(AE) 2023 Table 9.8.4.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Going (tread), minimum255 mmNBC(AE) 2023 Table 9.8.4.2 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Going (tread), maximum355 mmNBC(AE) 2023 Table 9.8.4.2 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Stair width, minimum860 mmNBC(AE) 2023 9.8.2.1.(2) (opens in a new tab)secondaryExit stairs serving a single dwelling unit or a house with a secondary suite
Stair headroom, minimum1950 mm (1.95 m)NBC(AE) 2023 9.8.2.2.(3) (opens in a new tab)secondaryStairs serving a single dwelling unit or a house with a secondary suite
Handrail height, minimum865 mmNBC(AE) 2023 9.8.7.4 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Guard height, minimum900 mmNBC(AE) 2023 9.8.8.3 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Guard height, higher walking surface1070 mm (1.07 m)NBC(AE) 2023 9.8.8.3 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Taller guard above ground level of1800 mm (1.8 m)NBC(AE) 2023 9.8.8.3 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Guard needed from a drop of600 mmNBC(AE) 2023 9.8.8.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Window fall protection, opening lower than this above the floor900 mmNBC(AE) 2023 9.8.8.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Window fall protection, opening higher than this above the ground1800 mm (1.8 m)NBC(AE) 2023 9.8.8.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Escape opening, area0.35 m²NBC(AE) 2023 9.9.10.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Escape opening, width380 mmNBC(AE) 2023 9.9.10.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Escape opening, height380 mmNBC(AE) 2023 9.9.10.1 (opens in a new tab)unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it
Secondary suite separation, sound transmission class, minimum43NBC(AE) 2023 9.11.1.1.(2) (opens in a new tab)secondaryOr the listed resilient-channel assembly
Secondary suite separation, apparent sound transmission class, minimum40NBC(AE) 2023 9.11.1.1.(2) (opens in a new tab)secondary
Ceiling height, habitable rooms1950 mm (1.95 m)not checked yetNBC(AE) 2023 9.5.3.1.(2) (opens in a new tab)unverifiedceilings in a secondary suite; 1850 mm under beams and ducts (9.5.3.1.(3)): the ceiling check does not tell a suite from the rest of the house

CCQ Chapitre I (Québec)

CCQ Chapitre I (Québec): Québec (Part 9 houses)
RuleValueClauseEvidence
Riser, minimum125 mmCCQ 2020 (CNB 2020 modifié) Table 9.8.4.1 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Riser, maximum200 mmCCQ 2020 (CNB 2020 modifié) Table 9.8.4.1 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Going (tread), minimum255 mmCCQ 2020 (CNB 2020 modifié) Table 9.8.4.2 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Going (tread), maximum355 mmCCQ 2020 (CNB 2020 modifié) Table 9.8.4.2 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Stair width, minimum860 mmCCQ 2020 (CNB 2020 modifié) 9.8.2.1 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Stair headroom, minimum1950 mm (1.95 m)CCQ 2020 (CNB 2020 modifié) 9.8.2.2 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Handrail height, minimum865 mmCCQ 2020 (CNB 2020 modifié) 9.8.7.4 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Guard height, minimum900 mmCCQ 2020 (CNB 2020 modifié) 9.8.8.3 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Guard height, higher walking surface1070 mm (1.07 m)CCQ 2020 (CNB 2020 modifié) 9.8.8.3 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Taller guard above ground level of1800 mm (1.8 m)CCQ 2020 (CNB 2020 modifié) 9.8.8.3 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Guard needed from a drop of600 mmCCQ 2020 (CNB 2020 modifié) 9.8.8.1 (opens in a new tab)unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened
Window fall protection, opening lower than this above the floor900 mmnot checked yetCCQ 2020 (CNB 2020 modifié) 9.8.8.1.(4) (opens in a new tab)unverifiedQuebec rewords window fall protection; not checked
Escape opening, area0.35 m²not checked yetCCQ 2020 (CNB 2020 modifié) 9.9.10.1.(1) (opens in a new tab)unverifiedQuebec exempts some floors from the bedroom escape window; not checked

UK Approved Documents (England)

UK Approved Documents (England): England only (Wales, Scotland, Northern Ireland and Ireland have their own rules)
RuleValueClauseEvidence
Riser, minimum150 mmAD K 2013 Table 1.1 (opens in a new tab)primary
Riser, maximum220 mmAD K 2013 Table 1.1 (opens in a new tab)primary
Going (tread), minimum220 mmAD K 2013 Table 1.1 (opens in a new tab)primary
Going (tread), maximum300 mmAD K 2013 Table 1.1 (opens in a new tab)primary
Stair pitch, maximum42°AD K 2013 Table 1.1, note (opens in a new tab)primary
Step formula 2R + G, minimum550 mmAD K 2013 Table 1.1, note (opens in a new tab)primary
Step formula 2R + G, maximum700 mmAD K 2013 Table 1.1, note (opens in a new tab)primary
Stair headroom, minimum2000 mm (2 m)AD K 2013 Diagram 1.3 (opens in a new tab)primary
Handrail height, minimum900 mmAD K 2013 para 1.34 (opens in a new tab)primary
Handrail height, maximum1000 mm (1 m)AD K 2013 para 1.34 (opens in a new tab)primary
Guard height, minimum1100 mm (1.1 m)AD K 2013 Diagram 3.1 (opens in a new tab)primary
Risers in consecutive flights, maximum36AD K 2013 para 1.17 (opens in a new tab)unverifieda change of direction after 36 risers in consecutive flights; paragraph number not confirmed
Bedroom, minimum floor area7.5 m²NDSS 2015 para 10 (opens in a new tab)secondarya planning standard, not Building Regulations
Kids room, minimum floor area7.5 m²NDSS 2015 para 10 (opens in a new tab)secondarya planning standard, not Building Regulations
Bedroom, minimum width2150 mm (2.15 m)NDSS 2015 para 10 (opens in a new tab)secondarya planning standard, not Building Regulations
Kids room, minimum width2150 mm (2.15 m)NDSS 2015 para 10 (opens in a new tab)secondarya planning standard, not Building Regulations
Escape opening, area0.33 m²AD B 2019 para 2.10 (opens in a new tab)primary
Escape opening, width450 mmAD B 2019 para 2.10 (opens in a new tab)primary
Escape opening, height450 mmAD B 2019 para 2.10 (opens in a new tab)primary
Escape opening, highest sill1100 mm (1.1 m)AD B 2019 para 2.10 (opens in a new tab)primary
Escape window rule applies up to a floor height of4.5 mAD B 2019 paras 2.1–2.5 (opens in a new tab)primary
Guard needed from a drop of600 mmnot checked yetAD K 2013 section 3 (opens in a new tab)unverifiednot yet confirmed against the text

DIN 18065 + MBO (Germany)

DIN 18065 + MBO (Germany): Germany (Austria and Switzerland have their own codes; Länder may differ)
RuleValueClauseEvidence
Riser, minimum14 cm (140 mm)DIN 18065 2020-08 Table 1 (opens in a new tab)secondary
Riser, maximum20 cm (200 mm)DIN 18065 2020-08 Table 1 (opens in a new tab)secondary
Going (tread), minimum23 cm (230 mm)DIN 18065 2020-08 Table 1 (opens in a new tab)secondary
Going (tread), maximum37 cm (370 mm)DIN 18065 2020-08 Table 1 (opens in a new tab)secondary
Stair width, minimum80 cm (800 mm)DIN 18065 2020-08 Table 1 (opens in a new tab)secondary
Stair headroom, minimum200 cm (2 m)DIN 18065 2020-08 6.4 (opens in a new tab)secondary
Handrail height, minimum80 cm (800 mm)DIN 18065 2020-08 handrail (opens in a new tab)secondary
Handrail height, maximum115 cm (1.15 m)DIN 18065 2020-08 handrail (opens in a new tab)secondary
Guard height, minimum90 cm (900 mm)MBO 2002/2024 §38(4) (opens in a new tab)unverifiedLänder building codes may differ
Guard height, higher walking surface110 cm (1.1 m)not checked yetMBO 2002/2024 §38(4) (opens in a new tab)unverifiednot yet modelled (110 cm above 1200 cm)
Ceiling height, habitable rooms240 cm (2.4 m)not checked yetMBO 2002/2024 §47 (opens in a new tab)unverifiedfrom memory; not confirmed

CDMX Reglamento (Mexico City)

CDMX Reglamento (Mexico City): Mexico City only (other states have their own reglamentos)
RuleValueClauseEvidence
Riser, minimum10 cm (100 mm)NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab)primary
Riser, maximum18 cm (180 mm)NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab)primary
Going (tread), minimum25 cm (250 mm)NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab)primary
Stair headroom, minimum210 cm (2.1 m)NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab)primary
Stair width, minimum900 mmNTC 2024 Tabla 4.3.5.2 (opens in a new tab)primary
Guard height, minimum90 cm (900 mm)NTC 2024 2.2.2.14.1(a) (opens in a new tab)primary
Handrail height, minimum85 cm (850 mm)NTC 2024 2.2.2.13.1(a) (opens in a new tab)primary
Handrail height, maximum95 cm (950 mm)NTC 2024 2.2.2.13.1(a) (opens in a new tab)primary
Handrail needed from this many risers4NTC 2024 2.2.2.5.1(c) (opens in a new tab)primaryThe NTC says more than 3 steps (escalones); read here as 4 or more risers, which is the same count when the top is a floor
Rise of one flight, maximum270 cm (2.7 m)NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab)primary
Ceiling height, habitable rooms230 cm (2.3 m)NTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Ceiling height, bathrooms and laundry210 cm (2.1 m)NTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Bedroom, minimum floor area6 m²NTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Bedroom, minimum width2.2 mNTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Kids room, minimum floor area6 m²NTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Kids room, minimum width2.2 mNTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Living room, minimum floor area6.75 m²NTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Living room, minimum width2.5 mNTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Dining room, minimum floor area4.8 m²NTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Dining room, minimum width2.4 mNTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Kitchen, minimum floor area3.75 m²NTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Kitchen, minimum width1.55 mNTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Utility, minimum floor area2.2 m²NTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary
Utility, minimum width1.55 mNTC 2024 Tabla 2.2.1.1 (opens in a new tab)primary

COE São Paulo (Brazil)

COE São Paulo (Brazil): São Paulo city only (other cities have their own Código de Obras)
RuleValueClauseEvidence
Bedroom, minimum floor area5 m²COE SP 2017 5.A.6 (opens in a new tab)secondary
Bedroom, minimum width2 mCOE SP 2017 5.A.6 (opens in a new tab)secondaryThe code asks for a 2.00 m circle inside the room; checked as 2.00 m across
Kids room, minimum floor area5 m²COE SP 2017 5.A.6 (opens in a new tab)secondary
Kids room, minimum width2 mCOE SP 2017 5.A.6 (opens in a new tab)secondaryThe code asks for a 2.00 m circle inside the room; checked as 2.00 m across
Living room, minimum floor area5 m²COE SP 2017 5.A.6 (opens in a new tab)secondary
Living room, minimum width2 mCOE SP 2017 5.A.6 (opens in a new tab)secondaryThe code asks for a 2.00 m circle inside the room; checked as 2.00 m across
Ceiling height, habitable rooms2.5 mCOE SP 2017 5.A.6 (opens in a new tab)secondaryThe 5.A.6 row covers bedrooms and living rooms (repouso, estar); FloorGen applies the same 2.50 m to dining rooms and studies
Ceiling height, kitchens2.5 mNBR 15575-1 2013 16.1 (opens in a new tab)secondaryKitchens are not on the standard’s reduced list, so they keep the habitable 2.50 m
Ceiling height, hallways2.3 mNBR 15575-1 2013 16.1 (opens in a new tab)secondary
Ceiling height, bathrooms and laundry2.3 mNBR 15575-1 2013 16.1 (opens in a new tab)secondarySet for instalações sanitárias; laundries are not on the reduced list, so they are under-checked at 2.30 m
Guard height, minimum110 cm (1.1 m)not checked yetNBR 14718 2019 guard height (opens in a new tab)unverifiedOnly trade and maker sites back it; the ABNT text is paid
Riser, minimum16 cm (160 mm)not checked yetNBR 9050 2020 6.8 (opens in a new tab)unverifiedNBR 9050 is the accessibility standard for public and shared use, not houses; copies disagree on the sub-clause
Riser, maximum18 cm (180 mm)not checked yetNBR 9050 2020 6.8 (opens in a new tab)unverifiedNBR 9050 is the accessibility standard for public and shared use, not houses; copies disagree on the sub-clause
Going (tread), minimum28 cm (280 mm)not checked yetNBR 9050 2020 6.8 (opens in a new tab)unverifiedNBR 9050 is the accessibility standard for public and shared use, not houses; copies disagree on the sub-clause
Going (tread), maximum32 cm (320 mm)not checked yetNBR 9050 2020 6.8 (opens in a new tab)unverifiedNBR 9050 is the accessibility standard for public and shared use, not houses; copies disagree on the sub-clause

CCH (France)

CCH (France): France (stair rules bind new homes built to sell or let; a house you build for yourself is exempt)
RuleValueClauseEvidence
Guard height, minimum1 mCCH 2021 R.134-59 (opens in a new tab)secondaryR.111-15 before 1 July 2021; 0.80 m where the guard is over 0.50 m thick (not modelled); the ground floor is exempt, but every balcony is checked
Riser, maximum18 cm (180 mm)Arrêté 2015 art. 12 (opens in a new tab)secondary
Going (tread), minimum24 cm (240 mm)Arrêté 2015 art. 12 (opens in a new tab)secondary
Stair width, minimum0.8 m (800 mm)Arrêté 2015 art. 12 (opens in a new tab)secondary
Wheelchair turning circle, diameter1.5 mArrêté 2015 art. 13 and annex 2 (opens in a new tab)secondarya turning space of 1.50 m diameter in the bathroom of a home on the ground floor or served by a lift; a kitchen needs a 1.50 m passage and a WC 0.80 × 1.30 m beside the bowl, not checked
Guard needed from a drop of1 mnot checked yetNF P01-012 2024 fall height (opens in a new tab)unverifiedcommercial sources only; NF standards are contractual, not law

SP 55 (Russia, houses)

SP 55 (Russia, houses): Russia, single-family houses (apartments follow SP 54)
RuleValueClauseEvidence
Guard height, minimum0.9 m (900 mm)SP 55 2016 (Change 2, 2023) 8.3 (opens in a new tab)secondaryStairs, balconies, loggias, terraces and other dangerous drops; no taller guard for upper floors
Ceiling height, habitable rooms2.5 mSP 55 2016 (Change 2, 2023) 6.2 (opens in a new tab)secondaryLiving rooms and kitchens; the 2.7 m of climate regions IА, IБ, IГ and IД (Change 2; the 2016 and 2018 texts named IIА) is not modelled
Ceiling height, hallways2.1 mSP 55 2016 (Change 2, 2023) 6.2 (opens in a new tab)secondaryCorridors
Stair width, minimum0.9 m (900 mm)not checked yetSP 54 2022 table 6.1 (opens in a new tab)unverifiedstairs inside an apartment; SP 55 8.2 gives no stair numbers and 7.5 leaves the width and slope of an escape stair unregulated
Stair pitch, maximum38.7°not checked yetSP 54 2022 table 6.1 (opens in a new tab)unverified1:1.25; stairs inside an apartment; SP 55 8.2 gives no stair numbers and 7.5 leaves the width and slope of an escape stair unregulated
Bedroom, minimum floor area8 m²not checked yetSP 55 2016 (Change 2, 2023) 6.1 (opens in a new tab)unverified10 m² for two people; binds houses built with state or municipal money; a private house follows its design brief (apartments: SP 54 5.3)
Living room, minimum floor area16 m²not checked yetSP 55 2016 (Change 2, 2023) 6.1 (opens in a new tab)unverified14 m² in a one-room house; binds houses built with state or municipal money; a private house follows its design brief (apartments: SP 54 5.3)
Kitchen, minimum floor area8 m²not checked yetSP 55 2016 (Change 2, 2023) 6.1 (opens in a new tab)unverifiedbinds houses built with state or municipal money; a private house follows its design brief (apartments: SP 54 5.3)

Building Standards Act (Japan)

Building Standards Act (Japan): Japan (local authorities may add rules)
RuleValueClauseEvidence
Riser, maximum23 cm (230 mm)BSL Order 2026 Art. 23(1) proviso (opens in a new tab)secondaryHouse stairs (住宅の階段), not the shared stairs of apartment buildings
Going (tread), minimum15 cm (150 mm)BSL Order 2026 Art. 23(1) proviso (opens in a new tab)secondaryWinder treads are measured 30 cm from the narrow end (Art. 23(2))
Stair width, minimum75 cm (750 mm)BSL Order 2026 Art. 23(1) table (4) (opens in a new tab)secondaryHandrails projecting up to 10 cm are ignored in the width (Art. 23(3))
Rise of one flight, maximum4 mBSL Order 2026 Art. 24(1) (opens in a new tab)secondary
Ceiling height, habitable rooms2.1 mBSL Order 2026 Art. 21 (opens in a new tab)secondaryAverage height (volume / area) of a 居室, kitchens included; halls, baths and WCs are not 居室
Guard height, minimum1.1 mnot checked yetBSL Order 2026 Art. 126(1) (opens in a new tab)unverifiedbinds only buildings in the Art. 117 scope (3+ storeys, special buildings, over 1000 m²); a 2-storey house is outside it
Landing length, minimum1.2 mnot checked yetBSL Order 2026 Art. 24(2) (opens in a new tab)unverifiedonly for the landings Art. 24(1) requires (a flight rising over 4 m)

NCC (Australia)

NCC (Australia): Australia (NSW, Queensland, South Australia, Tasmania and the NT are still on NCC 2022)
RuleValueClauseEvidence
Riser, minimum115 mmNCC 2025 Table 11.2.2a (opens in a new tab)secondary
Riser, maximum190 mmNCC 2025 Table 11.2.2a (opens in a new tab)secondary
Going (tread), minimum240 mmNCC 2025 Table 11.2.2a (opens in a new tab)secondary
Going (tread), maximum355 mmNCC 2025 Table 11.2.2a (opens in a new tab)secondary
Step formula 2R + G, minimum550 mmNCC 2025 Table 11.2.2a (opens in a new tab)secondary
Step formula 2R + G, maximum700 mmNCC 2025 Table 11.2.2a (opens in a new tab)secondary
Handrail height, minimum865 mmNCC 2025 11.3.5(1)(c) (opens in a new tab)secondaryread in a guide that summarises NCC 2025 11.3.5
Guard height, minimum1 mNCC 2025 11.3.4 (opens in a new tab)secondary
Stair headroom, minimum2 mNCC 2022 10.3.1(1)(f) (opens in a new tab)secondaryread on the NCC 2022 page; the same in NCC 2025
Guard needed from a drop of1 mNCC 2022 11.3.3 (opens in a new tab)secondarya fall of 1 m or more; FloorGen asks for a guard above 1 m
Landing length, minimum750 mmNCC 2022 11.2.5 (opens in a new tab)secondary
Ceiling height, habitable rooms2.4 mnot checked yetNCC 2022 10.3.1 (opens in a new tab)unverifiedread in NCC 2022 only; not confirmed in NCC 2025
Ceiling height, kitchens2.1 mnot checked yetNCC 2022 10.3.1 (opens in a new tab)unverifiedread in NCC 2022 only; not confirmed in NCC 2025
Ceiling height, hallways2.1 mnot checked yetNCC 2022 10.3.1 (opens in a new tab)unverifiedread in NCC 2022 only; not confirmed in NCC 2025
Ceiling height, bathrooms and laundry2.1 mnot checked yetNCC 2022 10.3.1 (opens in a new tab)unverifiedread in NCC 2022 only; not confirmed in NCC 2025

Generic

Generic: no building code is cited. These are rules of thumb, not code limits.

  • Riser: 150–190 mm
  • Going (tread): 250–300 mm
  • Stair width: ≥ 800 mm
  • Headroom: ≥ 2 m
  • Guard height: ≥ 90 cm

Checks that are the same under every code

Fixed checks
CheckValue
Step formula 2R + T60 to 66 cm, about 63 cm is best (England and Australia use 2R + G of 550 to 700 mm instead, from AD K and the NCC, as a code limit)
Spiral and square spiral treads60 cm long or more (they are not width-checked)
Ramp slope1 in 12 (8.3%) or less
Lift cabin110 × 140 cm or more
Lift door80 cm wide or more, and no wider than its shaft wall less 10 cm
Door approach75 cm clear on each side of a door or passage
Walkways75 cm or more between furniture, or furniture and a wall

An escape opening must be in an outside wall: a wall that no other enclosed room shares, or a wall onto a balcony or a window well. Sizes are the clear opening, the part that opens. A casement counts in full, a double-hung window half its height and a slider half its width. With the Generic profile, stair messages give the comfortable range instead of citing a code. See The Review panel for what triggers each warning.

Which code a new project starts on

The region picks it. A project in the United States starts on the IRC, Canada on NBC Canada 2020, the UK and Ireland on the UK Approved Documents, Germany, Austria and Switzerland on DIN 18065 + MBO, Mexico on the CDMX rules, Brazil on the São Paulo Código de Obras, France on the CCH, Russia on SP 55, Japan on the Building Standards Act and Australia on the NCC. Other regions start on Generic. A template drawn for a code keeps it only when the project’s region is Generic, so a US template there stays on the IRC. In a region with a code of its own, the template takes that code. In a region with no profile yet, such as Benelux, it gets Generic, and the region tab says so. Change the region in Settings (⌘,) on the Region tab.

Code audit

On plans that include it, a Code audit checks the whole home or one floor against the rulebook you pick and lists what to fix and review, with the rule behind each finding. See Run a code audit.

A starting point, not a permit check

The profiles use the published minimums for homes. Codes change and towns add their own rules, so check the current edition before you file.

Questions

My project uses NBC India 2016. Where did it go?

NBC India 2016 is no longer offered for new projects. A project saved on it keeps it, and its checks still run: risers up to 19 cm, treads from 25 cm, 1 m stairs, 2.2 m headroom, 90 cm handrails, 1 m balcony guards and room minimums for habitable rooms, kitchens, baths and stores.

Why is my bedroom not checked for size?

Only rooms with a Room type the code lists are checked. Give the room the type Bedroom in its properties. Some codes, such as NBC Canada 2020, set no room sizes at all.

Do I get messages in feet and inches?

Yes. Messages follow the project’s units, with ft² for areas in an imperial project.

Does changing the code change my plan?

No. It only changes what the checks measure against. Your walls, stairs and rooms stay as they are.