Building code profiles
Updated 5 min readWorks without an account
A building code profile sets the numbers the Review panel checks your stairs, railings, rooms and escape windows against. Pick the code for where you will build, from the IRC in the US to the Approved Documents in England.
Choose a building code

- Step 1: Open the plan summary
Click the chip at the top left that shows the area and rooms, or press ⌥3.
- Step 2: Find Building code
Scroll to Building. Below the areas, pick a code in Building code. The line under it sums up its main rules.
- Step 3: Check the plan again
Open Review with ⇧I. Every check now uses the new code, and the messages cite its sections.
The codes on offer
Each table lists the rules one profile checks, with the value as the source prints it, the clause it comes from and how sure we are. Messages show values in the project’s units. A rule a code does not set is not in its table and is not checked against that code. The fixed checks below apply under every code, and Generic lists rules of thumb because it cites no code. Room sizes apply only to rooms with that Room type.
Sources and how sure we are. Every number comes from a published document, cited with its edition and clause. Evidence “primary” means we read the value in the document itself. Evidence “secondary” means we read it in a copy, such as an adopting jurisdiction’s text or a reliable summary. Evidence “unverified” means we have not yet confirmed it in the current edition, and the note says why. Rules marked not checked yet are listed because the code sets them, but FloorGen does not measure your plan against them, so they never raise a warning.
IRC (US)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, maximum | 7¾ in (197 mm) | IRC 2021 R311.7.5.1 (opens in a new tab) | primary |
| Going (tread), minimum | 10 in (254 mm) | IRC 2021 R311.7.5.2 (opens in a new tab) | primary |
| Stair width, minimum | 36 in (914 mm) | IRC 2021 R311.7.1 (opens in a new tab) | primary |
| Spiral stair riser, maximum | 9½ in (241 mm) | IRC 2021 R311.7.10.1 (opens in a new tab) | secondarytreads are measured on the walkline, 12 in out from the column (its radius held to 24½ in); headroom 6 ft 6 in is not checked |
| Spiral stair tread at the walking line, minimum | 6¾ in (171 mm) | IRC 2021 R311.7.10.1 (opens in a new tab) | secondarytreads are measured on the walkline, 12 in out from the column (its radius held to 24½ in); headroom 6 ft 6 in is not checked |
| Spiral stair clear width, minimum | 26 in (660 mm) | IRC 2021 R311.7.10.1 (opens in a new tab) | secondarytreads are measured on the walkline, 12 in out from the column (its radius held to 24½ in); headroom 6 ft 6 in is not checked |
| Stair headroom, minimum | 80 in (2.032 m) | IRC 2021 R311.7.2 (opens in a new tab) | primary |
| Landing length, minimum | 36 in (914 mm) | IRC 2021 R311.7.6 (opens in a new tab) | primary |
| Handrail height, minimum | 34 in (864 mm) | IRC 2021 R311.7.8.1 (opens in a new tab) | primary |
| Handrail height, maximum | 38 in (965 mm) | IRC 2021 R311.7.8.1 (opens in a new tab) | primary |
| Handrail needed from this many risers | 4 | IRC 2021 R311.7.8 (opens in a new tab) | secondary |
| Guard height, minimum | 36 in (914 mm) | IRC 2021 R312.1.2 (opens in a new tab) | primary |
| Guard needed from a drop of | 30 in (762 mm) | IRC 2021 R312.1.1 (opens in a new tab) | primary |
| Rise of one flight, maximum | 151 in (3.835 m) | IRC 2021 R311.7.3 (opens in a new tab) | primary |
| Bedroom, minimum floor area | 70 ft² (6.5 m²) | IRC 2021 R304.1 (opens in a new tab) | primary |
| Living room, minimum floor area | 70 ft² (6.5 m²) | IRC 2021 R304.1 (opens in a new tab) | primary |
| Dining room, minimum floor area | 70 ft² (6.5 m²) | IRC 2021 R304.1 (opens in a new tab) | primary |
| Study, minimum floor area | 70 ft² (6.5 m²) | IRC 2021 R304.1 (opens in a new tab) | primary |
| Kids room, minimum floor area | 70 ft² (6.5 m²) | IRC 2021 R304.1 (opens in a new tab) | primary |
| Bedroom, minimum width | 7 ft (2.134 m) | IRC 2021 R304.2 (opens in a new tab) | primary |
| Living room, minimum width | 7 ft (2.134 m) | IRC 2021 R304.2 (opens in a new tab) | primary |
| Dining room, minimum width | 7 ft (2.134 m) | IRC 2021 R304.2 (opens in a new tab) | primary |
| Study, minimum width | 7 ft (2.134 m) | IRC 2021 R304.2 (opens in a new tab) | primary |
| Kids room, minimum width | 7 ft (2.134 m) | IRC 2021 R304.2 (opens in a new tab) | primary |
| Ceiling height, habitable rooms | 84 in (2.134 m) | IRC 2021 R305.1 (opens in a new tab) | primary |
| Ceiling height, bathrooms and laundry | 80 in (2.032 m) | IRC 2021 R305.1 (opens in a new tab) | primary |
| Ceiling height, other basement rooms | 80 in (2.032 m) | IRC 2021 R305.1.1 (opens in a new tab) | primary |
| Escape opening, area | 5.7 ft² (0.53 m²) | IRC 2021 R310.2.1 (opens in a new tab) | primary |
| Escape opening, area on the grade floor | 5 ft² (0.46 m²) | IRC 2021 R310.2.1 (opens in a new tab) | primary |
| Escape opening, width | 20 in (508 mm) | IRC 2021 R310.2.2 (opens in a new tab) | primary |
| Escape opening, height | 24 in (610 mm) | IRC 2021 R310.2.2 (opens in a new tab) | primary |
| Escape opening, highest sill | 44 in (1.118 m) | IRC 2021 R310.2.3 (opens in a new tab) | primary |
| Wall outlet, farthest from any point along the wall | 6 ft (1.829 m) | IRC 2021 E3901.2 (opens in a new tab) | secondary |
| Wall space that needs outlets, from a width of | 2 ft (610 mm) | IRC 2021 E3901.2 (opens in a new tab) | secondary |
| Floor outlet counts for a wall within | 18 in (457 mm) | IRC 2021 E3901.2 (opens in a new tab) | secondary |
| Escape opening counts as grade-floor within this height of the ground | 44 in (1.118 m) | IRC 2021 R202 (opens in a new tab) | secondaryDefinition read in an ICC 2018 summary; the 2021 exception names grade-floor openings only |
| Window fall protection, opening lower than this above the floor | 24 in (610 mm) | IRC 2021 R312.2.1 (opens in a new tab) | primary |
| Window fall protection, opening higher than this above the ground | 72 in (1.829 m) | IRC 2021 R312.2.1 (opens in a new tab) | primary |
| Hallway width, minimum | 3 ft (914 mm) | IRC 2021 R311.6 (opens in a new tab) | primary |
| Openings from a garage into a bedroom, allowed | 0 | IRC 2021 R302.5.1 (opens in a new tab) | secondary |
| Window glass, share of floor area, minimum | 8% | IRC 2021 R303.1 (opens in a new tab) | secondary |
| Openable window area, share of floor area, minimum | 4% | IRC 2021 R303.1 (opens in a new tab) | secondary |
| Egress door to outside, clear width | 32 in (813 mm) | IRC 2021 R311.2 (opens in a new tab) | primary |
| Egress door to outside, clear height | 78 in (1.981 m) | IRC 2021 R311.2 (opens in a new tab) | primary |
| Bathroom window glass without an exhaust fan, minimum | 3 ft² (0.28 m²) | IRC 2021 R303.3 (opens in a new tab) | primaryhalf of it openable; not needed with artificial light and a local exhaust to outdoors |
| WC or basin centreline to a side wall or fixture, minimum | 15 in (381 mm) | IRC 2021 P2705.1 (opens in a new tab) | primary |
| Clear floor in front of a WC or basin, minimum | 21 in (533 mm) | IRC 2021 P2705.1 (opens in a new tab) | primary |
| Clear floor in front of a shower opening, minimum | 24 in (610 mm) | IRC 2021 R307.1 (opens in a new tab) | primaryFigure R307.1: clear in front of the shower opening |
| Shower floor area, minimum | 900 in² (0.58 m²) | IRC 2021 P2708.1 (opens in a new tab) | primaryfinished interior, kept with a fold-down seat folded up |
| Shower, smallest side | 30 in (762 mm) | IRC 2021 P2708.1 (opens in a new tab) | primary |
| Shower, smallest side with the larger floor | 25 in (635 mm) | IRC 2021 P2708.1 (opens in a new tab) | primaryexception 2 |
| Shower floor area with a narrower side, minimum | 1300 in² (0.84 m²) | IRC 2021 P2708.1 (opens in a new tab) | primaryexception 2 |
NBC Canada 2020
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, minimum | 125 mm | NBC 2020 Table 9.8.4.1 (opens in a new tab) | secondary |
| Riser, maximum | 200 mm | NBC 2020 Table 9.8.4.1 (opens in a new tab) | secondary |
| Going (tread), minimum | 255 mm | NBC 2020 Table 9.8.4.2 (opens in a new tab) | secondary |
| Going (tread), maximum | 355 mm | NBC 2020 Table 9.8.4.2 (opens in a new tab) | secondary |
| Stair width, minimum | 860 mm | NBC 2020 9.8.2.1 (opens in a new tab) | secondary |
| Stair headroom, minimum | 1950 mm (1.95 m) | NBC 2020 9.8.2.2 (opens in a new tab) | secondary |
| Handrail height, minimum | 865 mm | NBC 2020 9.8.7.4 (opens in a new tab) | secondary |
| Guard height, minimum | 900 mm | NBC 2020 9.8.8.3 (opens in a new tab) | primarywithin dwelling units, and outside where the walking surface is at most 1800 mm above the ground |
| Guard height, higher walking surface | 1070 mm (1.07 m) | NBC 2020 9.8.8.3 (opens in a new tab) | primary |
| Taller guard above ground level of | 1800 mm (1.8 m) | NBC 2020 9.8.8.3 (opens in a new tab) | primary |
| Escape opening, area | 0.35 m² | NBC 2020 9.9.10.1 (opens in a new tab) | primarynot required where the suite is sprinklered (Sentence (1)), which the plan does not record |
| Escape opening, width | 380 mm | NBC 2020 9.9.10.1 (opens in a new tab) | primary |
| Escape opening, height | 380 mm | NBC 2020 9.9.10.1 (opens in a new tab) | primary |
| Guard needed from a drop of | 600 mm | NBC 2020 9.8.8.1 (opens in a new tab) | primary |
| Window fall protection, opening lower than this above the floor | 900 mm | NBC 2020 9.8.8.1 (opens in a new tab) | primarySentence (5): openable windows in residential occupancies; a guard or a 100 mm opening limit |
| Window fall protection, opening higher than this above the ground | 1800 mm (1.8 m) | NBC 2020 9.8.8.1 (opens in a new tab) | primary |
| Ceiling height, habitable rooms | 2100 mm (2.1 m) | NBC 2020 Table 9.5.3.1 (opens in a new tab) | primaryliving, dining, kitchen, bedrooms, other habitable rooms, halls; 1.95 m in a secondary suite (9.5.3.1.(2)) is not modelled |
| Secondary suite separation, sound transmission class, minimum | 43 | NBC 2020 9.11.1.1.(2) (opens in a new tab) | secondaryHouse with a secondary suite: construction with an STC of at least 43, or the listed resilient-channel assembly |
| Secondary suite separation, apparent sound transmission class, minimum | 40 | NBC 2020 9.11.1.1.(2) (opens in a new tab) | secondaryOr a separating assembly and adjoining constructions with an ASTC of at least 40 |
| Handrail height, maximum | 1070 mm (1.07 m)not checked yet | NBC 2020 9.8.7.4 (opens in a new tab) | unverified865–965 mm in general and 1070 mm on a guard per some readings, 1070 mm per the BCBC copy: sources disagree |
| Ceiling height, bathrooms and laundry | 2100 mm (2.1 m)not checked yet | NBC 2020 Table 9.5.3.1 (opens in a new tab) | unverifiedbathrooms, WCs and laundries above grade only; the check does not yet tell above-grade wet rooms from basement ones |
| Window well, clear space in front of an escape window | 760 mmnot checked yet | NBC 2020 9.9.10.1 (opens in a new tab) | unverifiedclear space in front of an escape window that opens into a well (Sentence (3)), read in the 2020 text; window wells are not checked yet |
OBC (Ontario)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, minimum | 125 mm | OBC 2024 Table 9.8.4.1 (opens in a new tab) | unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text |
| Riser, maximum | 200 mm | OBC 2024 Table 9.8.4.1 (opens in a new tab) | unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text |
| Going (tread), minimum | 255 mm | OBC 2024 Table 9.8.4.2 (opens in a new tab) | unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text |
| Going (tread), maximum | 355 mm | OBC 2024 Table 9.8.4.2 (opens in a new tab) | unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text |
| Stair width, minimum | 860 mm | OBC 2024 9.8.2.1 (opens in a new tab) | unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text |
| Stair headroom, minimum | 1950 mm (1.95 m) | OBC 2024 9.8.2.2 (opens in a new tab) | unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text |
| Handrail height, minimum | 865 mm | OBC 2024 9.8.7.4 (opens in a new tab) | unverifiedAssumed equal to NBC Part 9; not yet confirmed in the 2024 OBC text |
| Guard height, minimum | 900 mm | OBC 2024 9.8.8.3 (opens in a new tab) | secondary |
| Guard height, higher walking surface | 1070 mm (1.07 m) | OBC 2024 9.8.8.3 (opens in a new tab) | secondary |
| Taller guard above ground level of | 1800 mm (1.8 m) | OBC 2024 9.8.8.3 (opens in a new tab) | secondary |
| Guard needed from a drop of | 600 mm | OBC 2024 9.8.8.1 (opens in a new tab) | secondary |
| Window fall protection, opening lower than this above the floor | 900 mm | OBC 2024 9.8.8.1 (opens in a new tab) | secondarySentence (5), as the NBC; 480 mm was the 2012 OBC |
| Window fall protection, opening higher than this above the ground | 1800 mm (1.8 m) | OBC 2024 9.8.8.1 (opens in a new tab) | secondary |
| Escape opening, area | 0.35 m² | OBC 2024 9.9.10.1 (opens in a new tab) | secondary |
| Escape opening, width | 380 mm | OBC 2024 9.9.10.1 (opens in a new tab) | secondary |
| Escape opening, height | 380 mm | OBC 2024 9.9.10.1 (opens in a new tab) | secondary |
| Escape opening, highest sill | 1000 mm (1 m) | OBC 2024 9.9.10.1 (opens in a new tab) | secondary |
| Living room, minimum floor area | 13.5 m²not checked yet | OBC 2024 9.5.3A.1 (opens in a new tab) | unverified11 m² where living, dining and kitchen are combined in a unit sleeping two or fewer; smaller allowed where shown adequate (9.5.1.3) |
| Bedroom, minimum floor area | 7 m²not checked yet | OBC 2024 9.5.3D.1 (opens in a new tab) | unverified6 m² with built-in cabinets; one bedroom 9.8 m² (8.8 m² with built-ins, 9.5.3D.2); 4.2 m² combined with another space (9.5.3D.3) |
| Kitchen, minimum floor area | 4.2 m²not checked yet | OBC 2024 9.5.3C.1 (opens in a new tab) | unverified3.7 m² in a unit sleeping two or fewer |
| Dining room, minimum floor area | 7 m²not checked yet | OBC 2024 9.5.3B.1 (opens in a new tab) | unverifiedas a separate room; 3.25 m² combined with another space |
| Ceiling height, habitable rooms | 2300 mm (2.3 m)not checked yet | OBC 2024 Table 9.5.3.1 (opens in a new tab) | unverifiedover 75% of the required area of living, dining and kitchen spaces, 2100 mm at any point; bedrooms 2300 mm over 50% or 2100 mm over all; part-room heights and the per-room split are not modelled |
| Window well, clear space in front of an escape window | 550 mmnot checked yet | OBC 2024 9.9.10.1 (opens in a new tab) | unverifiedSentence (3), clear space in front of an escape window that opens into a well (760 mm in the NBC); window wells are not checked yet |
BCBC (British Columbia)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, minimum | 125 mm | BCBC 2024 9.8.4.1 (opens in a new tab) | secondaryPrivate stairs, as summarised for secondary suites |
| Riser, maximum | 200 mm | BCBC 2024 9.8.4.1 (opens in a new tab) | secondaryPrivate stairs, as summarised for secondary suites |
| Going (tread), minimum | 255 mm | BCBC 2024 Table 9.8.4.2 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same) |
| Going (tread), maximum | 355 mm | BCBC 2024 Table 9.8.4.2 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same) |
| Stair width, minimum | 860 mm | BCBC 2024 9.8.2.1.(2) (opens in a new tab) | secondaryExit stairs serving a house with a secondary suite |
| Stair headroom, minimum | 1950 mm (1.95 m) | BCBC 2024 9.8.2.2.(3) (opens in a new tab) | secondaryStairs serving a house with a secondary suite |
| Handrail height, minimum | 865 mm | BCBC 2024 9.8.7.4 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same) |
| Guard height, minimum | 900 mm | BCBC 2024 9.8.8.3 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same) |
| Guard height, higher walking surface | 1070 mm (1.07 m) | BCBC 2024 9.8.8.3 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same) |
| Taller guard above ground level of | 1800 mm (1.8 m) | BCBC 2024 9.8.8.3 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same) |
| Guard needed from a drop of | 600 mm | BCBC 2024 9.8.8.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same) |
| Window fall protection, opening lower than this above the floor | 900 mm | BCBC 2024 9.8.8.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same) |
| Window fall protection, opening higher than this above the ground | 1800 mm (1.8 m) | BCBC 2024 9.8.8.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; not confirmed in the 2024 BCBC text (the 2018 BCBC reads the same) |
| Escape opening, area | 0.35 m² | BCBC 2024 9.9.10.1 (opens in a new tab) | secondaryBedroom window; summarised for secondary suites |
| Escape opening, width | 380 mm | BCBC 2024 9.9.10.1 (opens in a new tab) | secondaryNo dimension under 380 mm |
| Escape opening, height | 380 mm | BCBC 2024 9.9.10.1 (opens in a new tab) | secondaryNo dimension under 380 mm |
| Secondary suite separation, fire-resistance rating, lowest option (minutes) | 15 | BCBC 2024 9.10.9.16 (opens in a new tab) | secondaryMinutes. 15 where every smoke alarm in the house is photo-electric and interconnected (9.10.19.5.(2)); 30 with an extra photo-electric alarm in each unit and common space; 45 otherwise; none if sprinklered |
| Secondary suite separation, fire-resistance rating with no alarm or sprinkler credit (minutes) | 45 | BCBC 2024 9.10.9.16 (opens in a new tab) | secondaryMinutes, with no alarm or sprinkler credit (9.10.19.5.(3)) |
| Secondary suite separation, sound transmission class, minimum | 43 | BCBC 2024 9.11.1.1.(2) (opens in a new tab) | secondaryOr the listed resilient-channel assembly |
| Secondary suite separation, apparent sound transmission class, minimum | 40 | BCBC 2024 9.11.1.1.(2) (opens in a new tab) | secondary |
| Handrail height, maximum | 1070 mm (1.07 m)not checked yet | BCBC 2024 9.8.7.4.(2) (opens in a new tab) | unverified865 to 1070 mm in the 2018 BCBC; the 2024 text was not opened |
NBC Alberta Edition 2023
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, minimum | 125 mm | NBC(AE) 2023 Table 9.8.4.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Riser, maximum | 200 mm | NBC(AE) 2023 Table 9.8.4.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Going (tread), minimum | 255 mm | NBC(AE) 2023 Table 9.8.4.2 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Going (tread), maximum | 355 mm | NBC(AE) 2023 Table 9.8.4.2 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Stair width, minimum | 860 mm | NBC(AE) 2023 9.8.2.1.(2) (opens in a new tab) | secondaryExit stairs serving a single dwelling unit or a house with a secondary suite |
| Stair headroom, minimum | 1950 mm (1.95 m) | NBC(AE) 2023 9.8.2.2.(3) (opens in a new tab) | secondaryStairs serving a single dwelling unit or a house with a secondary suite |
| Handrail height, minimum | 865 mm | NBC(AE) 2023 9.8.7.4 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Guard height, minimum | 900 mm | NBC(AE) 2023 9.8.8.3 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Guard height, higher walking surface | 1070 mm (1.07 m) | NBC(AE) 2023 9.8.8.3 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Taller guard above ground level of | 1800 mm (1.8 m) | NBC(AE) 2023 9.8.8.3 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Guard needed from a drop of | 600 mm | NBC(AE) 2023 9.8.8.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Window fall protection, opening lower than this above the floor | 900 mm | NBC(AE) 2023 9.8.8.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Window fall protection, opening higher than this above the ground | 1800 mm (1.8 m) | NBC(AE) 2023 9.8.8.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Escape opening, area | 0.35 m² | NBC(AE) 2023 9.9.10.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Escape opening, width | 380 mm | NBC(AE) 2023 9.9.10.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Escape opening, height | 380 mm | NBC(AE) 2023 9.9.10.1 (opens in a new tab) | unverifiedAssumed equal to NBC 2020; the Alberta text was not opened for it |
| Secondary suite separation, sound transmission class, minimum | 43 | NBC(AE) 2023 9.11.1.1.(2) (opens in a new tab) | secondaryOr the listed resilient-channel assembly |
| Secondary suite separation, apparent sound transmission class, minimum | 40 | NBC(AE) 2023 9.11.1.1.(2) (opens in a new tab) | secondary |
| Ceiling height, habitable rooms | 1950 mm (1.95 m)not checked yet | NBC(AE) 2023 9.5.3.1.(2) (opens in a new tab) | unverifiedceilings in a secondary suite; 1850 mm under beams and ducts (9.5.3.1.(3)): the ceiling check does not tell a suite from the rest of the house |
CCQ Chapitre I (Québec)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, minimum | 125 mm | CCQ 2020 (CNB 2020 modifié) Table 9.8.4.1 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Riser, maximum | 200 mm | CCQ 2020 (CNB 2020 modifié) Table 9.8.4.1 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Going (tread), minimum | 255 mm | CCQ 2020 (CNB 2020 modifié) Table 9.8.4.2 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Going (tread), maximum | 355 mm | CCQ 2020 (CNB 2020 modifié) Table 9.8.4.2 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Stair width, minimum | 860 mm | CCQ 2020 (CNB 2020 modifié) 9.8.2.1 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Stair headroom, minimum | 1950 mm (1.95 m) | CCQ 2020 (CNB 2020 modifié) 9.8.2.2 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Handrail height, minimum | 865 mm | CCQ 2020 (CNB 2020 modifié) 9.8.7.4 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Guard height, minimum | 900 mm | CCQ 2020 (CNB 2020 modifié) 9.8.8.3 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Guard height, higher walking surface | 1070 mm (1.07 m) | CCQ 2020 (CNB 2020 modifié) 9.8.8.3 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Taller guard above ground level of | 1800 mm (1.8 m) | CCQ 2020 (CNB 2020 modifié) 9.8.8.3 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Guard needed from a drop of | 600 mm | CCQ 2020 (CNB 2020 modifié) 9.8.8.1 (opens in a new tab) | unverifiedNBC 2020 value; Quebec amends the NBC and its own Part 9 text was not opened |
| Window fall protection, opening lower than this above the floor | 900 mmnot checked yet | CCQ 2020 (CNB 2020 modifié) 9.8.8.1.(4) (opens in a new tab) | unverifiedQuebec rewords window fall protection; not checked |
| Escape opening, area | 0.35 m²not checked yet | CCQ 2020 (CNB 2020 modifié) 9.9.10.1.(1) (opens in a new tab) | unverifiedQuebec exempts some floors from the bedroom escape window; not checked |
UK Approved Documents (England)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, minimum | 150 mm | AD K 2013 Table 1.1 (opens in a new tab) | primary |
| Riser, maximum | 220 mm | AD K 2013 Table 1.1 (opens in a new tab) | primary |
| Going (tread), minimum | 220 mm | AD K 2013 Table 1.1 (opens in a new tab) | primary |
| Going (tread), maximum | 300 mm | AD K 2013 Table 1.1 (opens in a new tab) | primary |
| Stair pitch, maximum | 42° | AD K 2013 Table 1.1, note (opens in a new tab) | primary |
| Step formula 2R + G, minimum | 550 mm | AD K 2013 Table 1.1, note (opens in a new tab) | primary |
| Step formula 2R + G, maximum | 700 mm | AD K 2013 Table 1.1, note (opens in a new tab) | primary |
| Stair headroom, minimum | 2000 mm (2 m) | AD K 2013 Diagram 1.3 (opens in a new tab) | primary |
| Handrail height, minimum | 900 mm | AD K 2013 para 1.34 (opens in a new tab) | primary |
| Handrail height, maximum | 1000 mm (1 m) | AD K 2013 para 1.34 (opens in a new tab) | primary |
| Guard height, minimum | 1100 mm (1.1 m) | AD K 2013 Diagram 3.1 (opens in a new tab) | primary |
| Risers in consecutive flights, maximum | 36 | AD K 2013 para 1.17 (opens in a new tab) | unverifieda change of direction after 36 risers in consecutive flights; paragraph number not confirmed |
| Bedroom, minimum floor area | 7.5 m² | NDSS 2015 para 10 (opens in a new tab) | secondarya planning standard, not Building Regulations |
| Kids room, minimum floor area | 7.5 m² | NDSS 2015 para 10 (opens in a new tab) | secondarya planning standard, not Building Regulations |
| Bedroom, minimum width | 2150 mm (2.15 m) | NDSS 2015 para 10 (opens in a new tab) | secondarya planning standard, not Building Regulations |
| Kids room, minimum width | 2150 mm (2.15 m) | NDSS 2015 para 10 (opens in a new tab) | secondarya planning standard, not Building Regulations |
| Escape opening, area | 0.33 m² | AD B 2019 para 2.10 (opens in a new tab) | primary |
| Escape opening, width | 450 mm | AD B 2019 para 2.10 (opens in a new tab) | primary |
| Escape opening, height | 450 mm | AD B 2019 para 2.10 (opens in a new tab) | primary |
| Escape opening, highest sill | 1100 mm (1.1 m) | AD B 2019 para 2.10 (opens in a new tab) | primary |
| Escape window rule applies up to a floor height of | 4.5 m | AD B 2019 paras 2.1–2.5 (opens in a new tab) | primary |
| Guard needed from a drop of | 600 mmnot checked yet | AD K 2013 section 3 (opens in a new tab) | unverifiednot yet confirmed against the text |
DIN 18065 + MBO (Germany)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, minimum | 14 cm (140 mm) | DIN 18065 2020-08 Table 1 (opens in a new tab) | secondary |
| Riser, maximum | 20 cm (200 mm) | DIN 18065 2020-08 Table 1 (opens in a new tab) | secondary |
| Going (tread), minimum | 23 cm (230 mm) | DIN 18065 2020-08 Table 1 (opens in a new tab) | secondary |
| Going (tread), maximum | 37 cm (370 mm) | DIN 18065 2020-08 Table 1 (opens in a new tab) | secondary |
| Stair width, minimum | 80 cm (800 mm) | DIN 18065 2020-08 Table 1 (opens in a new tab) | secondary |
| Stair headroom, minimum | 200 cm (2 m) | DIN 18065 2020-08 6.4 (opens in a new tab) | secondary |
| Handrail height, minimum | 80 cm (800 mm) | DIN 18065 2020-08 handrail (opens in a new tab) | secondary |
| Handrail height, maximum | 115 cm (1.15 m) | DIN 18065 2020-08 handrail (opens in a new tab) | secondary |
| Guard height, minimum | 90 cm (900 mm) | MBO 2002/2024 §38(4) (opens in a new tab) | unverifiedLänder building codes may differ |
| Guard height, higher walking surface | 110 cm (1.1 m)not checked yet | MBO 2002/2024 §38(4) (opens in a new tab) | unverifiednot yet modelled (110 cm above 1200 cm) |
| Ceiling height, habitable rooms | 240 cm (2.4 m)not checked yet | MBO 2002/2024 §47 (opens in a new tab) | unverifiedfrom memory; not confirmed |
CDMX Reglamento (Mexico City)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, minimum | 10 cm (100 mm) | NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab) | primary |
| Riser, maximum | 18 cm (180 mm) | NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab) | primary |
| Going (tread), minimum | 25 cm (250 mm) | NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab) | primary |
| Stair headroom, minimum | 210 cm (2.1 m) | NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab) | primary |
| Stair width, minimum | 900 mm | NTC 2024 Tabla 4.3.5.2 (opens in a new tab) | primary |
| Guard height, minimum | 90 cm (900 mm) | NTC 2024 2.2.2.14.1(a) (opens in a new tab) | primary |
| Handrail height, minimum | 85 cm (850 mm) | NTC 2024 2.2.2.13.1(a) (opens in a new tab) | primary |
| Handrail height, maximum | 95 cm (950 mm) | NTC 2024 2.2.2.13.1(a) (opens in a new tab) | primary |
| Handrail needed from this many risers | 4 | NTC 2024 2.2.2.5.1(c) (opens in a new tab) | primaryThe NTC says more than 3 steps (escalones); read here as 4 or more risers, which is the same count when the top is a floor |
| Rise of one flight, maximum | 270 cm (2.7 m) | NTC 2024 Tabla 2.2.2.5.1 (opens in a new tab) | primary |
| Ceiling height, habitable rooms | 230 cm (2.3 m) | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Ceiling height, bathrooms and laundry | 210 cm (2.1 m) | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Bedroom, minimum floor area | 6 m² | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Bedroom, minimum width | 2.2 m | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Kids room, minimum floor area | 6 m² | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Kids room, minimum width | 2.2 m | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Living room, minimum floor area | 6.75 m² | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Living room, minimum width | 2.5 m | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Dining room, minimum floor area | 4.8 m² | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Dining room, minimum width | 2.4 m | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Kitchen, minimum floor area | 3.75 m² | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Kitchen, minimum width | 1.55 m | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Utility, minimum floor area | 2.2 m² | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
| Utility, minimum width | 1.55 m | NTC 2024 Tabla 2.2.1.1 (opens in a new tab) | primary |
COE São Paulo (Brazil)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Bedroom, minimum floor area | 5 m² | COE SP 2017 5.A.6 (opens in a new tab) | secondary |
| Bedroom, minimum width | 2 m | COE SP 2017 5.A.6 (opens in a new tab) | secondaryThe code asks for a 2.00 m circle inside the room; checked as 2.00 m across |
| Kids room, minimum floor area | 5 m² | COE SP 2017 5.A.6 (opens in a new tab) | secondary |
| Kids room, minimum width | 2 m | COE SP 2017 5.A.6 (opens in a new tab) | secondaryThe code asks for a 2.00 m circle inside the room; checked as 2.00 m across |
| Living room, minimum floor area | 5 m² | COE SP 2017 5.A.6 (opens in a new tab) | secondary |
| Living room, minimum width | 2 m | COE SP 2017 5.A.6 (opens in a new tab) | secondaryThe code asks for a 2.00 m circle inside the room; checked as 2.00 m across |
| Ceiling height, habitable rooms | 2.5 m | COE SP 2017 5.A.6 (opens in a new tab) | secondaryThe 5.A.6 row covers bedrooms and living rooms (repouso, estar); FloorGen applies the same 2.50 m to dining rooms and studies |
| Ceiling height, kitchens | 2.5 m | NBR 15575-1 2013 16.1 (opens in a new tab) | secondaryKitchens are not on the standard’s reduced list, so they keep the habitable 2.50 m |
| Ceiling height, hallways | 2.3 m | NBR 15575-1 2013 16.1 (opens in a new tab) | secondary |
| Ceiling height, bathrooms and laundry | 2.3 m | NBR 15575-1 2013 16.1 (opens in a new tab) | secondarySet for instalações sanitárias; laundries are not on the reduced list, so they are under-checked at 2.30 m |
| Guard height, minimum | 110 cm (1.1 m)not checked yet | NBR 14718 2019 guard height (opens in a new tab) | unverifiedOnly trade and maker sites back it; the ABNT text is paid |
| Riser, minimum | 16 cm (160 mm)not checked yet | NBR 9050 2020 6.8 (opens in a new tab) | unverifiedNBR 9050 is the accessibility standard for public and shared use, not houses; copies disagree on the sub-clause |
| Riser, maximum | 18 cm (180 mm)not checked yet | NBR 9050 2020 6.8 (opens in a new tab) | unverifiedNBR 9050 is the accessibility standard for public and shared use, not houses; copies disagree on the sub-clause |
| Going (tread), minimum | 28 cm (280 mm)not checked yet | NBR 9050 2020 6.8 (opens in a new tab) | unverifiedNBR 9050 is the accessibility standard for public and shared use, not houses; copies disagree on the sub-clause |
| Going (tread), maximum | 32 cm (320 mm)not checked yet | NBR 9050 2020 6.8 (opens in a new tab) | unverifiedNBR 9050 is the accessibility standard for public and shared use, not houses; copies disagree on the sub-clause |
CCH (France)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Guard height, minimum | 1 m | CCH 2021 R.134-59 (opens in a new tab) | secondaryR.111-15 before 1 July 2021; 0.80 m where the guard is over 0.50 m thick (not modelled); the ground floor is exempt, but every balcony is checked |
| Riser, maximum | 18 cm (180 mm) | Arrêté 2015 art. 12 (opens in a new tab) | secondary |
| Going (tread), minimum | 24 cm (240 mm) | Arrêté 2015 art. 12 (opens in a new tab) | secondary |
| Stair width, minimum | 0.8 m (800 mm) | Arrêté 2015 art. 12 (opens in a new tab) | secondary |
| Wheelchair turning circle, diameter | 1.5 m | Arrêté 2015 art. 13 and annex 2 (opens in a new tab) | secondarya turning space of 1.50 m diameter in the bathroom of a home on the ground floor or served by a lift; a kitchen needs a 1.50 m passage and a WC 0.80 × 1.30 m beside the bowl, not checked |
| Guard needed from a drop of | 1 mnot checked yet | NF P01-012 2024 fall height (opens in a new tab) | unverifiedcommercial sources only; NF standards are contractual, not law |
SP 55 (Russia, houses)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Guard height, minimum | 0.9 m (900 mm) | SP 55 2016 (Change 2, 2023) 8.3 (opens in a new tab) | secondaryStairs, balconies, loggias, terraces and other dangerous drops; no taller guard for upper floors |
| Ceiling height, habitable rooms | 2.5 m | SP 55 2016 (Change 2, 2023) 6.2 (opens in a new tab) | secondaryLiving rooms and kitchens; the 2.7 m of climate regions IА, IБ, IГ and IД (Change 2; the 2016 and 2018 texts named IIА) is not modelled |
| Ceiling height, hallways | 2.1 m | SP 55 2016 (Change 2, 2023) 6.2 (opens in a new tab) | secondaryCorridors |
| Stair width, minimum | 0.9 m (900 mm)not checked yet | SP 54 2022 table 6.1 (opens in a new tab) | unverifiedstairs inside an apartment; SP 55 8.2 gives no stair numbers and 7.5 leaves the width and slope of an escape stair unregulated |
| Stair pitch, maximum | 38.7°not checked yet | SP 54 2022 table 6.1 (opens in a new tab) | unverified1:1.25; stairs inside an apartment; SP 55 8.2 gives no stair numbers and 7.5 leaves the width and slope of an escape stair unregulated |
| Bedroom, minimum floor area | 8 m²not checked yet | SP 55 2016 (Change 2, 2023) 6.1 (opens in a new tab) | unverified10 m² for two people; binds houses built with state or municipal money; a private house follows its design brief (apartments: SP 54 5.3) |
| Living room, minimum floor area | 16 m²not checked yet | SP 55 2016 (Change 2, 2023) 6.1 (opens in a new tab) | unverified14 m² in a one-room house; binds houses built with state or municipal money; a private house follows its design brief (apartments: SP 54 5.3) |
| Kitchen, minimum floor area | 8 m²not checked yet | SP 55 2016 (Change 2, 2023) 6.1 (opens in a new tab) | unverifiedbinds houses built with state or municipal money; a private house follows its design brief (apartments: SP 54 5.3) |
Building Standards Act (Japan)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, maximum | 23 cm (230 mm) | BSL Order 2026 Art. 23(1) proviso (opens in a new tab) | secondaryHouse stairs (住宅の階段), not the shared stairs of apartment buildings |
| Going (tread), minimum | 15 cm (150 mm) | BSL Order 2026 Art. 23(1) proviso (opens in a new tab) | secondaryWinder treads are measured 30 cm from the narrow end (Art. 23(2)) |
| Stair width, minimum | 75 cm (750 mm) | BSL Order 2026 Art. 23(1) table (4) (opens in a new tab) | secondaryHandrails projecting up to 10 cm are ignored in the width (Art. 23(3)) |
| Rise of one flight, maximum | 4 m | BSL Order 2026 Art. 24(1) (opens in a new tab) | secondary |
| Ceiling height, habitable rooms | 2.1 m | BSL Order 2026 Art. 21 (opens in a new tab) | secondaryAverage height (volume / area) of a 居室, kitchens included; halls, baths and WCs are not 居室 |
| Guard height, minimum | 1.1 mnot checked yet | BSL Order 2026 Art. 126(1) (opens in a new tab) | unverifiedbinds only buildings in the Art. 117 scope (3+ storeys, special buildings, over 1000 m²); a 2-storey house is outside it |
| Landing length, minimum | 1.2 mnot checked yet | BSL Order 2026 Art. 24(2) (opens in a new tab) | unverifiedonly for the landings Art. 24(1) requires (a flight rising over 4 m) |
NCC (Australia)
| Rule | Value | Clause | Evidence |
|---|---|---|---|
| Riser, minimum | 115 mm | NCC 2025 Table 11.2.2a (opens in a new tab) | secondary |
| Riser, maximum | 190 mm | NCC 2025 Table 11.2.2a (opens in a new tab) | secondary |
| Going (tread), minimum | 240 mm | NCC 2025 Table 11.2.2a (opens in a new tab) | secondary |
| Going (tread), maximum | 355 mm | NCC 2025 Table 11.2.2a (opens in a new tab) | secondary |
| Step formula 2R + G, minimum | 550 mm | NCC 2025 Table 11.2.2a (opens in a new tab) | secondary |
| Step formula 2R + G, maximum | 700 mm | NCC 2025 Table 11.2.2a (opens in a new tab) | secondary |
| Handrail height, minimum | 865 mm | NCC 2025 11.3.5(1)(c) (opens in a new tab) | secondaryread in a guide that summarises NCC 2025 11.3.5 |
| Guard height, minimum | 1 m | NCC 2025 11.3.4 (opens in a new tab) | secondary |
| Stair headroom, minimum | 2 m | NCC 2022 10.3.1(1)(f) (opens in a new tab) | secondaryread on the NCC 2022 page; the same in NCC 2025 |
| Guard needed from a drop of | 1 m | NCC 2022 11.3.3 (opens in a new tab) | secondarya fall of 1 m or more; FloorGen asks for a guard above 1 m |
| Landing length, minimum | 750 mm | NCC 2022 11.2.5 (opens in a new tab) | secondary |
| Ceiling height, habitable rooms | 2.4 mnot checked yet | NCC 2022 10.3.1 (opens in a new tab) | unverifiedread in NCC 2022 only; not confirmed in NCC 2025 |
| Ceiling height, kitchens | 2.1 mnot checked yet | NCC 2022 10.3.1 (opens in a new tab) | unverifiedread in NCC 2022 only; not confirmed in NCC 2025 |
| Ceiling height, hallways | 2.1 mnot checked yet | NCC 2022 10.3.1 (opens in a new tab) | unverifiedread in NCC 2022 only; not confirmed in NCC 2025 |
| Ceiling height, bathrooms and laundry | 2.1 mnot checked yet | NCC 2022 10.3.1 (opens in a new tab) | unverifiedread in NCC 2022 only; not confirmed in NCC 2025 |
Generic
Generic: no building code is cited. These are rules of thumb, not code limits.
- Riser: 150–190 mm
- Going (tread): 250–300 mm
- Stair width: ≥ 800 mm
- Headroom: ≥ 2 m
- Guard height: ≥ 90 cm
Checks that are the same under every code
| Check | Value |
|---|---|
| Step formula 2R + T | 60 to 66 cm, about 63 cm is best (England and Australia use 2R + G of 550 to 700 mm instead, from AD K and the NCC, as a code limit) |
| Spiral and square spiral treads | 60 cm long or more (they are not width-checked) |
| Ramp slope | 1 in 12 (8.3%) or less |
| Lift cabin | 110 × 140 cm or more |
| Lift door | 80 cm wide or more, and no wider than its shaft wall less 10 cm |
| Door approach | 75 cm clear on each side of a door or passage |
| Walkways | 75 cm or more between furniture, or furniture and a wall |
An escape opening must be in an outside wall: a wall that no other enclosed room shares, or a wall onto a balcony or a window well. Sizes are the clear opening, the part that opens. A casement counts in full, a double-hung window half its height and a slider half its width. With the Generic profile, stair messages give the comfortable range instead of citing a code. See The Review panel for what triggers each warning.
Which code a new project starts on
The region picks it. A project in the United States starts on the IRC, Canada on NBC Canada 2020, the UK and Ireland on the UK Approved Documents, Germany, Austria and Switzerland on DIN 18065 + MBO, Mexico on the CDMX rules, Brazil on the São Paulo Código de Obras, France on the CCH, Russia on SP 55, Japan on the Building Standards Act and Australia on the NCC. Other regions start on Generic. A template drawn for a code keeps it only when the project’s region is Generic, so a US template there stays on the IRC. In a region with a code of its own, the template takes that code. In a region with no profile yet, such as Benelux, it gets Generic, and the region tab says so. Change the region in Settings (⌘,) on the Region tab.
Code audit
On plans that include it, a Code audit checks the whole home or one floor against the rulebook you pick and lists what to fix and review, with the rule behind each finding. See Run a code audit.
A starting point, not a permit check
The profiles use the published minimums for homes. Codes change and towns add their own rules, so check the current edition before you file.Questions
My project uses NBC India 2016. Where did it go?
NBC India 2016 is no longer offered for new projects. A project saved on it keeps it, and its checks still run: risers up to 19 cm, treads from 25 cm, 1 m stairs, 2.2 m headroom, 90 cm handrails, 1 m balcony guards and room minimums for habitable rooms, kitchens, baths and stores.
Why is my bedroom not checked for size?
Only rooms with a Room type the code lists are checked. Give the room the type Bedroom in its properties. Some codes, such as NBC Canada 2020, set no room sizes at all.
Do I get messages in feet and inches?
Yes. Messages follow the project’s units, with ft² for areas in an imperial project.
Does changing the code change my plan?
No. It only changes what the checks measure against. Your walls, stairs and rooms stay as they are.
Try it on a sample house.
The 3-bed ranch template opens in the studio, free and without an account.